Gundersen Health System: Low-Energy Design and Renewable Energy at Sparta Clinic

Overview

As part of its Envision Sustainability Program, Gundersen Health System is pursuing energy efficiency through low-energy design standards coupled with renewable energy. Gundersen Health System’s 35,000-square-foot Sparta Medical Clinic, located in Sparta, Wisconsin, opened in January 2017. The clinic provides residents in and around Sparta with access to medical care, physical therapy, digital mammography, cardiac rehabilitation, and more. The clinic’s interior design is part of Gundersen’s commitment to improving the health of the environment and the communities it serves by powering its buildings with clean, renewable energy.

Sparta Clinic was built with sustainable design features aimed at achieving its energy usage goal of 35 kBtu/sq. ft. In May 2017, the clinic was certified LEED Gold for Building Design + Construction. It has already surpassed its energy savings goal by 9 percent after being open just over a year. Sparta Clinic was one of the organizations that was recognized at the USGBC Wisconsin’s Transformation Leadership Awards for successful sustainability practices and helping to drive the green transformation of Wisconsin. This early success was a result of facility and operational staff maintaining an “energy-conscious attitude.”

In Sparta Clinic’s design stage, a variety of sustainability features were considered and implemented to enable the clinic to generate its own energy and use as little power as possible. Starting with a goal of 35 kBtu/sq. ft. – a measurement of energy consumption that translates to 50 percent less than what the average clinic uses today – Sparta Clinic now only consumes 33 kBtu/sq. ft. The clinic integrates the use of both on-site and off-site solar, with a rooftop array of solar photovoltaic panels capable of producing 100 KW of energy and 220 KW of solar energy purchased from a nearby Xcel Energy community solar garden. The combination solar power generates enough renewable energy to offset the building’s consumption. As of June 2018, the solar photovoltaic panels have produced more energy than the building has consumed establishing the clinic as an energy independent facility. 

An additional renewable feature of the facility is the geothermal wells used for heating and cooling. The design team collaborated with an energy modeling consultant to evaluate two HVAC system options early on in construction, a central Air Handling Unit with Variable Air Volume systems, and a distributed geothermal heat pump system. A distributed system yielded a higher energy reduction of 15 kBtu/sq. ft. As a result, 40 geothermal wells, all 300 feet deep, were installed to heat and cool the building.

Gundersen met its goal in by combining solar and geothermal with a variety of energy efficiency building features:

 

Heating and Cooling

Decentralized heat-pump systemReduces fan power and moves air from cool space to warm areas and vice-versa
Heat recovery ventilation systemTransfers energy from exhaust air to incoming air during cool weather and from incoming air to exhaust air during warmer weather.
Ground source heat pumpServices the hot water heater a ground source heat pump was installed.

 

Building Materials

Spray foam insulationCovers gaps in the walls and reduces energy use by almost 5 kBtu/sq. ft.  with the same thermal resistance R value as rigid insulation.
Thermally broken door and window framesActs as insulating barriers between the inside and outside of the window and door frames.
Double pane windowsConserves energy in colder and warmer months

 

Lighting and Controls

Occupancy sensorsReduces lighting and HVAC use when space is not being utilized
LED interior/exterior lighting and controlsLED lighting with manual dimming were installed throughout the building. LED lighting was installed through the exterior to 6.87 kW, 50% below baseline allowance.
Building Automation SystemControls the mechanical system to employ advanced system optimization strategies.
Plug load controlsIT system power management software was integrated to ensure PC’s and monitors enter sleep mode resulting in a plug load reduction from 50% to 5% (6 kBtu/sq. ft. reduction).

 

Within a year, these efficiency measures have resulted in over $68,500 in savings for the Gundersen Health System.

 

Resources: